Full-load current by horsepower and voltage for single-phase and three-phase motors, with the 125% figure used for conductor and overload sizing.
Data verified 2026-09-29 · based on NEC 2023 (NFPA 70-2023)
| Horsepower[2] | 115 V 1φ A[2] | 230 V 1φ A[2] | 208 V 3φ A[2] | 230 V 3φ A[2] | 460 V 3φ A[2] | 575 V 3φ A[2] | 125% of 460 V A[1] |
|---|---|---|---|---|---|---|---|
| 0.5 # | 9.8 | 4.9 | 2.4 | 2.2 | 1.1 | 0.9 | 1.375 |
| 0.75 # | 13.8 | 6.9 | 3.5 | 3.2 | 1.6 | 1.3 | 2 |
| 1 # | 16 | 8 | 4.6 | 4.2 | 2.1 | 1.7 | 2.625 |
| 1.5 # | 20 | 10 | 6.6 | 6 | 3 | 2.4 | 3.75 |
| 2 # | 24 | 12 | 7.5 | 6.8 | 3.4 | 2.7 | 4.25 |
| 3 # | 34 | 17 | 10.6 | 9.6 | 4.8 | 3.9 | 6 |
| 5 # | 56 | 28 | 16.7 | 15.2 | 7.6 | 6.1 | 9.5 |
| 7.5 # | 80 | 40 | 24.2 | 22 | 11 | 9 | 13.75 |
| 10 # | 100 | 50 | 30.8 | 28 | 14 | 11 | 17.5 |
| 15 # | — | — | 46.2 | 42 | 21 | 17 | 26.25 |
| 20 # | — | — | 59.4 | 54 | 27 | 22 | 33.75 |
| 25 # | — | — | 74.8 | 68 | 34 | 27 | 42.5 |
| 30 # | — | — | 88 | 80 | 40 | 32 | 50 |
| 40 # | — | — | 114 | 104 | 52 | 41 | 65 |
| 50 # | — | — | 143 | 130 | 65 | 52 | 81.25 |
| 60 # | — | — | 169 | 154 | 77 | 62 | 96.25 |
| 75 # | — | — | 211 | 192 | 96 | 77 | 120 |
| 100 # | — | — | 273 | 248 | 124 | 99 | 155 |
| 125 # | — | — | 343 | 312 | 156 | 125 | 195 |
| 150 # | — | — | 396 | 360 | 180 | 144 | 225 |
| 200 # | — | — | 528 | 480 | 240 | 192 | 300 |
| 250 # | — | — | 675 | 604 | 302 | 242 | 377.5 |
These are Code table values, not nameplate values. A motor's nameplate current may be lower than the table figure, and the Code still requires the table value to be used for conductor sizing — the intent is that the circuit accommodates any motor of that rating, not just the efficient one installed today.
Single-phase motors above 10 HP are not tabulated because they are not commonly manufactured. Three-phase current falls roughly in proportion to voltage: 460 V draws half of 230 V, and 575 V draws about 40%.
The 125% column is the branch-circuit conductor and disconnect sizing figure for a motor with a marked temperature rise of 40 °C or less. Motors with higher temperature rise use different factors, and the overload relay is sized separately from the motor's nameplate service factor.
Motors of the same horsepower vary widely in efficiency, and therefore in current. An older standard-efficiency motor may draw 20% more than a premium-efficiency one of the same rating. If circuits were sized from the nameplate, replacing a motor with a less efficient one would overload the existing circuit.
Using a single tabulated figure for each horsepower and voltage means the circuit is adequate for any motor of that rating, and a swap does not require rewiring. The cost is that a modern high-efficiency motor leaves capacity unused — which is the intended trade.
The practical consequence: the branch circuit, disconnect and short-circuit protection are all sized from the table, while the overload relay is sized from the nameplate. That split is deliberate — the overload relay protects the specific motor, and the circuit protects the wiring.
Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | Value computed from the standard's defining relationship | derived | Computed at build time from the defining formula and checked against every row. |
| [2] | NEC Table 430.250 — Full-Load Current, Three-Phase Alternating-Current Motors | standard | NEC 2023 (NFPA 70-2023) |
| Standard | Revision | What it covers on this page |
|---|---|---|
| NEC Table 430.250 — Full-Load Current, Three-Phase Alternating-Current Motors | NEC 2023 (NFPA 70-2023) | the three-phase columns |
| NEC Table 430.248 — Full-Load Current, Single-Phase Alternating-Current Motors | NEC 2023 (NFPA 70-2023) | the single-phase columns |
| NEC Article 430.22 — Sizing Motor Branch-Circuit Conductors | NEC 2023 (NFPA 70-2023) | the 125% factor |
Cross-checked against:
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| 125% of 460 V current | 460 V three-phase full-load current × 1.25, the branch-circuit sizing factor. |
Values are Code table figures for general-purpose motors. Specific motor types — synchronous, wound-rotor, direct-current, or motors with unusual characteristics — are covered by different tables or by the manufacturer's data.
Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.