Engineering Reference

Insulation R-Value Chart

R-value per inch of thickness for 29 insulation materials and building products, from aerogel at R-10 per inch down to concrete at R-0.08.

Data verified 2026-09-29 · based on ASHRAE Handbook, 2021 Fundamentals volume

R-Value per Inch of Thickness

Material[1]Class[1]R per inch
h·ft²·°F/BTU·in[1]
RSI per 25 mm
K·m²/W[3]
RSI per m
K·m²/W[3]
Density
kg/m³[1]
Note[1]
Aerogel blanket #High performance10.001.73369.335140Highest R per inch available; costly and dusty to install
Polyurethane board (closed cell) #Rigid foam6.001.0441.60132Highest of the common rigid foams
Polyisocyanurate board #Rigid foam5.700.98839.52130Slightly lower than polyurethane; common in roofing
Closed-cell spray foam #Spray foam6.501.12745.06832Also acts as an air barrier and can add structural stiffness
Extruded polystyrene (XPS) #Rigid foam5.000.866734.66835Moisture resistant; the standard below-grade board
Expanded polystyrene (EPS) #Rigid foam3.850.667326.69420Cheaper than XPS and nearly as good when dry
Open-cell spray foam #Spray foam3.600.62424.9618Air barrier but not a vapour barrier; lower R per inch
Phenolic foam board #Rigid foam7.001.21348.53535High R per inch with good fire performance
Mineral wool batt #Fibrous batt3.300.57222.88140Non-combustible; better than glass at high temperature
Fibreglass batt (standard) #Fibrous batt3.140.544321.77110The baseline batt; R-13 for a 3.5 in wall cavity
Fibreglass batt (high density) #Fibrous batt3.800.658726.34720Fits the same cavity with higher R
Cellulose loose fill #Loose fill3.600.62424.96140Recycled paper with fire retardant; must be installed at the right density
Mineral wool loose fill #Loose fill3.000.5220.840Blown mineral wool; non-combustible
Fibreglass loose fill #Loose fill2.500.433317.33410Settles over time; install above the nominal thickness to compensate
Vermiculite loose fill #Loose fill2.200.381315.254100Largely historical; may contain asbestos in pre-1990 installations
Perlite loose fill #Loose fill2.700.46818.72100Lightweight mineral fill
Wood fibreboard #Structural board3.500.606724.267250Can serve as sheathing and insulation together
Cork board #Structural board3.600.62424.961120Renewable, dimensionally stable
Cotton batt (recycled denim) #Fibrous batt3.700.641325.65425Similar performance to fibreglass; requires careful fire treatment
Sheep wool batt #Fibrous batt3.600.62424.96125Moisture buffering; higher cost
Vacuum insulation panel #High performance25.004.333173.34200Highest R per inch by far, but loses most of it if punctured
Softwood lumber #Structural1.250.21678.6669500Timber is a poor insulator but a structural necessity
Plywood and OSB #Structural1.250.21678.6669600Similar to solid wood
Gypsum board #Structural0.900.1566.2402800Half-inch board is about R-0.45 total
Brick #Masonry0.200.034671.38671900Poor insulator; adds thermal mass rather than resistance
Concrete (normal weight) #Masonry0.080.013870.554682400Very poor per inch — an 8 in wall is only about R-0.6
Concrete block (hollow) #Masonry1.100.19077.62691200Empty cores help; filled or grouted block is closer to solid concrete
Stone #Masonry0.080.013870.554682700Similar to concrete
Glass (single pane) #Glazing0.020.0034670.138672500Essentially no insulating value; the air film does the work

R-value is a per-inch figure here, and total R is that number times the thickness. A material's rated R-value only applies at its stated thickness and installed density — loose fill installed below its rated density performs worse than the bag claims, and batts compressed into a cavity lose R in proportion to how much they are squeezed.

Two things this table does not capture. The first is air movement: fibrous insulation works by trapping air, so any convection loop inside it or air washing through it destroys a large part of its value — which is why an air barrier and a wind barrier matter as much as the R-value. The second is thermal bridging: studs, joists and slab edges conduct heat around the insulation, so an assembly's effective R is always lower than the insulation's nominal R.

R-value also falls with moisture and, for foams, with the ageing of the blowing agent. Polyisocyanurate in particular loses some of its rated R over the first few years as the low-conductivity gas escapes, which is why long-term values are quoted separately from initial ones.

R-Value, RSI and U-Factor

Three quantities describe the same physics in different units, and mixing them up is the usual error.

R-value is thermal resistance in imperial units, in h·ft²·°F/BTU. R-values add: a wall with R-13 insulation, R-0.5 sheathing and R-0.45 drywall has a total of about R-14 plus the surface films, before bridging is considered.

RSI is the same quantity in SI units, in K·m²/W. The conversion is 1 R = 0.176110 RSI, so R-13 is RSI 2.29. Because R is per inch and RSI is per metre of thickness in some tables and per 25 mm in others, always check which basis a metric figure uses.

U-factor is the reciprocal of total R, in BTU/h·ft²·°F. It describes how much heat flows, so lower is better — the opposite direction to R. A wall of total R-20 has a U of 0.05. U is what appears in heating and cooling load calculations, and it is what window ratings quote, because glazing is rated on heat flow rather than on resistance.

Keep them straight by remembering which direction is good: higher R is better, lower U is better.

Why the Assembly Always Performs Worse

The R-value on an insulation bag is measured on the insulation alone, in a laboratory, dry and undisturbed. An assembly in a real wall performs measurably worse, for three reasons that compound.

Thermal bridging. Studs at 16 in on centre occupy about 25% of a 2×4 wall's area and have an R-value of roughly 1.25 per inch against the insulation's 3.14. The framing short-circuits the insulation, and a nominal R-13 wall performs closer to R-11. Continuous exterior insulation, or advanced framing with studs at 24 in on centre, addresses this directly.

Air leakage. Fibrous insulation does nothing to stop air moving through it. A leaky wall loses far more heat to air exchange than to conduction through the insulation, which is why air sealing is usually the highest-return first step — and why it should come before adding more insulation.

Moisture. Wet insulation conducts much better than dry, and most fibrous materials lose a large fraction of their R when saturated. The design response is not more insulation but a correct vapour and drainage strategy, so the assembly dries rather than accumulates.

The practical order is: air seal first, then address bridging, then add insulation. Adding R to a leaky, bridged assembly delivers much less than the arithmetic suggests.

Frequently Asked Questions

What is the R-value of fibreglass insulation?
About R-3.14 per inch for standard batts and R-3.8 for high-density batts. A 3.5 in batt gives R-13 and a 5.5 in batt gives R-21 in the standard density. Loose-fill fibreglass is lower, around R-2.5 per inch, and settles over time.
What does R-value mean?
Thermal resistance — how well a material resists heat flow, in h·ft²·°F/BTU. Higher is better. R-values add when materials are layered, so a wall's total R is the sum of its layers plus the surface air films, before thermal bridging is accounted for.
How do I convert R-value to RSI?
Multiply by 0.176110. R-13 is RSI 2.29. RSI is in K·m²/W and is the SI equivalent. Watch the basis: some metric tables give RSI per metre of thickness and others per 25 mm, and confusing the two gives an answer off by a factor of 40.
Why is a wall's effective R lower than the insulation's R?
Mainly thermal bridging through the framing, which occupies about a quarter of the wall area with a material of less than half the R-value. Air leakage and moisture reduce it further. The rated R-value describes the insulation alone, dry, with no framing passing through it.
Is a higher R-value always better?
It reduces conduction heat loss, but the returns diminish and the cost does not. Air sealing and addressing thermal bridging usually deliver more per dollar than adding insulation beyond a certain point. There is also a point where extra internal insulation can create a moisture problem by making the sheathing too cold.
What is the difference between R-value and U-factor?
U-factor is the reciprocal of total R — it measures heat flow rather than resistance, so lower U is better. Windows are rated in U-factor because they are specified by how much heat they let through. R-20 corresponds to U-0.05.

Related

Value Sources

Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.

#SourceTypeRevision / method
[1]ASHRAE Handbook — Fundamentals, thermal insulation and building envelope chaptersstandardASHRAE Handbook, 2021 Fundamentals volume
[2]ASTM C518 — Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter ApparatusstandardASTM C518-21
[3]Value computed from the standard's defining relationshipderivedComputed at build time from the defining formula and verified against every row.

Data Sources

StandardRevisionWhat it covers on this page
ASHRAE Handbook — Fundamentals, thermal insulation and envelope chaptersASHRAE Handbook, 2021 Fundamentals volumethe R-values per inch of thickness
ASTM C518 — Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter ApparatusASTM C518-21the method behind the measured R-values
ASTM C168 — Standard Terminology Relating to Thermal InsulationASTM C168-19the definitions of R-value, RSI and U-factor

Cross-checked against:

Derived values — the following values on this page are calculated, not taken directly from the standard:

ValueHow it is derived
RSI per 25 mm and RSI per metreRSI = R × 0.176110, the exact conversion. The per-metre column is the per-25 mm column multiplied by 40. Both are recomputed at build time; the two bases are given separately because metric tables use each.

R-values are per inch of thickness for the material alone, dry and undisturbed. Installed performance is lower: loose fill installed below rated density underperforms, compressed batts lose R proportionally, foam loses some R as the blowing agent ages, and any assembly loses more to thermal bridging and air leakage. Total assembly R is not the sum of the insulation R-values.

Accuracy and use. The values on this page are compiled from the published standards and cross-checked sources listed above. Where values are derived, the derivation is stated. No warranty, express or implied, is made as to the accuracy or completeness of this information, and no liability is accepted for any loss or damage arising from its use. Engineering reference data is provided for guidance in preliminary work — before a value is used for design, fabrication or acceptance testing, verify it against the current revision of the governing standard and against your own inspection. The user assumes all risk and responsibility in connection with the use of this information.

Cite This Page

Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:

Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.