The standard ampere ratings for circuit breakers and fuses, with the continuous-load and inverse-time figures that follow from each.
Data verified 2026-09-29 · based on NEC 2023 (NFPA 70-2023)
| Standard rating[2] | Amperes[2] | Continuous load (80%) A[1] | Load at 125% A[1] | Typical application[2] |
|---|---|---|---|---|
| 15 A # | 15 | 12.0 | 18.8 | Branch circuits — receptacles, lighting, small appliances |
| 20 A # | 20 | 16.0 | 25.0 | Branch circuits — receptacles, lighting, small appliances |
| 25 A # | 25 | 20.0 | 31.2 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 30 A # | 30 | 24.0 | 37.5 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 35 A # | 35 | 28.0 | 43.8 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 40 A # | 40 | 32.0 | 50.0 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 45 A # | 45 | 36.0 | 56.2 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 50 A # | 50 | 40.0 | 62.5 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 60 A # | 60 | 48.0 | 75.0 | Larger branch circuits — ranges, dryers, subpanels, small motors |
| 70 A # | 70 | 56.0 | 87.5 | Subpanels and feeder circuits |
| 80 A # | 80 | 64.0 | 100.0 | Subpanels and feeder circuits |
| 90 A # | 90 | 72.0 | 112.5 | Subpanels and feeder circuits |
| 100 A # | 100 | 80.0 | 125.0 | Subpanels and feeder circuits |
| 110 A # | 110 | 88.0 | 137.5 | Service and feeder circuits, small commercial |
| 125 A # | 125 | 100.0 | 156.2 | Service and feeder circuits, small commercial |
| 150 A # | 150 | 120.0 | 187.5 | Service and feeder circuits, small commercial |
| 175 A # | 175 | 140.0 | 218.8 | Service and feeder circuits, small commercial |
| 200 A # | 200 | 160.0 | 250.0 | Service and feeder circuits, small commercial |
| 225 A # | 225 | 180.0 | 281.2 | Service and feeder circuits, small commercial |
| 250 A # | 250 | 200.0 | 312.5 | Commercial services and distribution |
| 300 A # | 300 | 240.0 | 375.0 | Commercial services and distribution |
| 350 A # | 350 | 280.0 | 437.5 | Commercial services and distribution |
| 400 A # | 400 | 320.0 | 500.0 | Commercial services and distribution |
| 450 A # | 450 | 360.0 | 562.5 | Large commercial and light industrial distribution |
| 500 A # | 500 | 400.0 | 625.0 | Large commercial and light industrial distribution |
| 600 A # | 600 | 480.0 | 750.0 | Large commercial and light industrial distribution |
| 700 A # | 700 | 560.0 | 875.0 | Large commercial and light industrial distribution |
| 800 A # | 800 | 640.0 | 1000.0 | Large commercial and light industrial distribution |
| 1000 A # | 1000 | 800.0 | 1250.0 | Industrial switchgear and main distribution |
| 1200 A # | 1200 | 960.0 | 1500.0 | Industrial switchgear and main distribution |
| 1600 A # | 1600 | 1280.0 | 2000.0 | Industrial switchgear and main distribution |
| 2000 A # | 2000 | 1600.0 | 2500.0 | Industrial switchgear and main distribution |
| 2500 A # | 2500 | 2000.0 | 3125.0 | Industrial switchgear and main distribution |
| 3000 A # | 3000 | 2400.0 | 3750.0 | Industrial switchgear and main distribution |
| 4000 A # | 4000 | 3200.0 | 5000.0 | Industrial switchgear and main distribution |
| 5000 A # | 5000 | 4000.0 | 6250.0 | Industrial switchgear and main distribution |
| 6000 A # | 6000 | 4800.0 | 7500.0 | Industrial switchgear and main distribution |
Breakers are manufactured only in the ratings listed — the series is fixed by NEC 240.6, not by what would be convenient. There is no 55 A, 65 A, 75 A or 90 A breaker in the standard series, so a calculated load must be rounded up to the next standard size.
The continuous-load column is 80% of the rating, because a breaker carrying a continuous load (three hours or more) may be loaded only to 80% of its rating unless the assembly is listed for 100%. Equivalently, the breaker must be at least 125% of the continuous load — which is the inverse-time column.
Standard ratings above 1,200 A are normally only available as adjustable-trip moulded case or insulated case breakers, where the rating is set within a range rather than fixed.
A branch circuit's overcurrent device must protect the conductor. The conductor's ampacity comes from the ampacity table, adjusted for ambient temperature and the number of conductors in the raceway — and the breaker must not exceed that adjusted ampacity.
The practical sequence is: calculate the load, apply the 125% factor for continuous loads, then select the next standard size up. That last step matters because the calculated figure almost never lands on a standard rating. A 42 A continuous load needs 52.5 A, which rounds to a 60 A breaker — and the conductor must then be sized to carry 60 A, not 52.5 A.
One exception is worth knowing: the next-size-up rule may be applied to the next standard rating only, not the one after. A load that needs 130 A cannot be served by a 150 A breaker on a 125 A conductor — the conductor must be increased instead.
Each data column on this page is tied to the source it came from. The numbers in square brackets correspond to the table headers above.
| # | Source | Type | Revision / method |
|---|---|---|---|
| [1] | Value computed from the standard's defining relationship | derived | Computed at build time from the defining formula and checked against every row. |
| [2] | NEC Article 240.6 — Standard Ampere Ratings for Fuses and Inverse Time Circuit Breakers | standard | NEC 2023 (NFPA 70-2023) |
| Standard | Revision | What it covers on this page |
|---|---|---|
| NEC Article 240.6 — Standard Ampere Ratings for Fuses and Inverse Time Circuit Breakers | NEC 2023 (NFPA 70-2023) | every rating in the table |
| NEC Article 210.20 — Overcurrent Protection for Branch Circuits | NEC 2023 (NFPA 70-2023) | the 125% continuous-load requirement |
| NEC Article 240.4 — Protection of Conductors | NEC 2023 (NFPA 70-2023) | the next-size-up allowance and its limits |
Cross-checked against:
Derived values — the following values on this page are calculated, not taken directly from the standard:
| Value | How it is derived |
|---|---|
| Continuous-load and 125% columns | 80% and 125% of the standard rating — exact reciprocals of each other. |
Ratings are the standard series only. Selecting a breaker requires the calculated load, the conductor ampacity after adjustment, and the applicable code article. Above 1,200 A most breakers are adjustable-trip and the rating is set rather than selected.
Every value on this page is traceable to the sources listed above. If you use the data in a document, paper or report, cite it as:
Each row in the tables above also has a permanent link — hover a row and use the # link to cite a single value rather than the whole page.
This site uses Google Analytics to count visits and see which pages are useful. It sets cookies only if you agree. See the privacy policy.